RCU host
RCU host: local scene engine, offline keep-alive, Modbus slave/gateway; per room or riser aggregation.
Intégration PMS hôtel et contrôle de chambre — interfaces Modbus, RS485, BACnet et BMS pour projets d'intégrateurs.
* Example mapping—not final register addresses; project Modbus table and DI/DO diagram after contract. Webhook / REST require project enablement.

Core tender and integration documentation—how platform events land on RCU hardware;specific addresses per project BOM appendix.
| Platform event | Integration method | RCU / register | Direction | Notes |
|---|---|---|---|---|
| Check-in | Modbus RTU/TCP | 0x0100room-state word | W | Triggers Welcome · seecard power |
| Check-out | Modbus | 0x0100 | W | Access revoke · vacant cutoff |
| Room VC / OCC / OOO | Modbus / API | 0x0101 | R/W | Align with PMS enum |
| DND / MUR | Dry contact + Modbus | DI-03 /0x0200 | R | Seedoor sign solution |
| Engineering / housekeeping card | Modbus | 0x0102 | W | Timed access · lock linkage |
| Device / scene | Integration method | RCU / register | Direction | Notes |
|---|---|---|---|---|
| Card power state | DI + Modbus | DI-01 /0x0300 | R | Card power logic |
| Lighting circuit ON/OFF | Modbus coil | 0x0001–0x0010 | R/W | Relay module mapping |
| FCU setpoint | Modbus holding register | 0x0400 | R/W | SeeHVAC |
| Trigger Welcome scene | Modbus / internal | 0x0500 | W | RCU local priority |
| Public schedule sync | Modbus / API | 0x0600block | W | Seepublic areas |
| Alarm / event | Integration method | RCU / register | Direction | Notes |
|---|---|---|---|---|
| SOS emergency | Dry contact DI | DI-08 | R → platform | DO output optional |
| Door contact abnormal open | DI + Webhook | DI-02 / REST | R | Vacant-room alarm |
| Device offline / heartbeat | REST API | /api/v1/heartbeat | R | Project enablement |
| Energy pulse / sub-meter | Modbus / DI | 0x0700 | R | Optional energy module |
| RCU firmware OTA | Integrator platform | — | — | Not bundled with hardware |
RCU host: local scene engine, offline keep-alive, Modbus slave/gateway; per room or riser aggregation.
Protocol conversion, multi-RCU aggregation, RS485 isolation; TCP/RTU dual mode; firewall policy by integrator.
Modbus modules,DI acquisition, relay expansion; address table with BOM.
| Capability | Point Pur Intelligent delivers | Integrator / client |
|---|---|---|
| RCU / modules / panels | ✓ hardware + wiring diagrams | Installation |
| Modbus register table | ✓ project documentation | Map to PMS/BMS |
| Local scenes / card power logic | ✓ RCU configuration | Policy confirmation |
| PMS / GRMS software | — | ✓ third party or custom |
| Room-state dashboard / NOC | — | ✓ integrator platform |
| Remote ops console | Optional capability | ✓ seecloud protocol guide |

PMS/BMS → integrator middleware → RCU/gateway → modules/panels/sensors. Bidirectional commands and status; scenes execute locally on RCU.

① single RCU scene acceptance → ② Modbus read/write → ③ PMS room mapping → ④ alarm Webhook → ⑤ offline regression.

After contract export Excel/PDF per model—coils and holding registers.
Same volume as per-room wiring—SOS/contact/card power terminals matched.
Project API key; heartbeat, room state, alarm push format on developer site.
Integrator supplies PMS simulator or test environment; Point Pur Intelligent aligns registers.